Florida HVAC technician reviewing an Air A and Air B HVAC exam practice test with tabbed mechanical code books

Florida HVAC Exam Practice Test: Free Air A & Air B Quiz

Take this free Florida HVAC exam practice test for Class A and Class B candidates. Review worked explanations and create your free account.

Pascual, Contractor Licensing Instructor
October 23, 2026 • 8 min read

Taking an HVAC exam practice test built around Florida's official reference list is the best way to measure your readiness for either the Class A (CAC) or Class B air conditioning contractor license. In Florida, both HVAC license categories require passing the 120 question Business and Finance exam plus a computer based Trade Knowledge exam at Pearson VUE with at least 70 percent. Every figure below was checked against Florida Statutes Section 489.105 and the DBPR Exam at a Glance summary in October 2026. Work through the seven original study practice questions below (not copied from the confidential state exam) to test your knowledge of tonnage limits, psychrometrics, ductwork, and refrigeration codes.

What Does the Florida Air Conditioning Exam Cover for Class A and Class B?

The Florida air conditioning exam splits into two separate trade tests depending on which license class you choose, though both cover the same nine subject areas under Rule 61G4-16.001. The Class A trade exam has 130 scored questions in 7.5 hours, while the Class B trade exam has 80 scored questions in 5 hours:

  • Installation of refrigeration and HVAC systems: 23 percent on Air A (22 percent on Air B)
  • Installation of HVAC equipment and components: 14 percent on both exams
  • Maintenance service of HVAC systems: 14 percent on both exams
  • Pre installation and design engineering: 12 percent on Air A (10 percent on Air B)
  • Ductwork and HVAC materials: 10 percent on Air A (12 percent on Air B)
  • Controls, energy management, and safety: remaining 27 to 28 percent across both tests

Compare both paths in our HVAC license Florida Air A vs Air B guide.

Brass and red/blue HVAC manifold gauges, infrared thermometer, tabbed mechanical code binder, and calculator on a study desk

How Does a Class A HVAC License Florida Scope Differ From Class B?

When preparing for an HVAC contractor license Florida candidates must know the exact statutory boundary between a Class A HVAC license Florida issues and a Class B license, because scope questions appear regularly on the exam. Under Florida Statutes Section 489.105(3)(f) and (g), the difference is system capacity, not building occupancy.

  • A Class A air conditioning contractor's services are unlimited in central air conditioning, refrigeration, heating, and ventilating systems, including boilers, unfired pressure vessels, and process piping.
  • A Class B air conditioning contractor is limited to 25 tons of cooling and 500,000 Btu of heating in any one system.
  • Neither Class A nor Class B may install potable water lines, sanitary sewer lines, or swimming pool piping, which must be subcontracted.
  • An active certified Class B contractor with at least one year of proven experience can upgrade to Class A by passing the Class A trade exam.

HVAC Exam Practice Test: Questions 1 and 2 (Scope & Load Math)

Start this HVAC exam practice test with statutory tonnage limits and sensible load math.

  • Question 1 (Capacity Limit): A Class B contractor bids on a building with three independent rooftop units, each rated at 20 tons cooling and 350,000 Btu heating. Under Section 489.105(3)(g), may the Class B contractor do this job? A) No, total is 60 tons. B) No, commercial work is excluded. C) Yes, the limit of 25 tons cooling and 500,000 Btu heating applies to any one system. D) Only with an engineer.
  • Answer 1: C. Section 489.105(3)(g) sets the limit at 25 tons cooling and 500,000 Btu heating per system.
  • Question 2 (Sensible Heat): What is the sensible heat gain in Btuh for 2,000 CFM when entering dry bulb is 80 degrees F and leaving is 55 degrees F (factor 1.08)? A) 36,000. B) 50,000. C) 54,000. D) 60,000.
  • Answer 2: C. Multiply 1.08 times 2,000 CFM times 25 degrees F = 54,000 Btuh.

Class B HVAC License Florida & Air A Practice: Questions 3 and 4

Whether you are targeting a Class B HVAC license Florida course or Class A, expect questions on condensate drains and duct support.

  • Question 3 (Condensate): Under FBC Mechanical Section 307, what is the minimum condensate drain pipe size for a 4 ton air handler, and what is required above a ceiling? A) 1/2 inch drain. B) 3/4 inch minimum internal diameter drain, plus a secondary drain or pan with a shutoff switch. C) 1.5 inch cast iron. D) 3/8 inch copper.
  • Answer 3: B. Section 307.2.2 requires a 3/4 inch internal diameter drain, plus secondary protection above ceilings.
  • Question 4 (Duct Sag): Under SMACNA and FBC Mechanical Chapter 6 rules for flexible ducts, what is the maximum permissible sag between hangers on horizontal runs? A) Zero sag. B) 1/2 inch per foot of support spacing. C) 3 inches per foot. D) 6 inches.
  • Answer 4: B. Flexible duct supports allow up to 1/2 inch of sag per foot.

Florida HVAC Exam Practice Questions 5 and 6 (Superheat & Ohm's Law)

These Florida HVAC exam practice items cover refrigeration superheat and low voltage control math.

  • Question 5 (Superheat): A technician reads a suction pressure corresponding to a saturation temperature of 40 degrees F on a PT chart, and measures a suction line temperature of 52 degrees F at the evaporator outlet. What is the superheat? A) 8 degrees F. B) 12 degrees F. C) 40 degrees F. D) 92 degrees F.
  • Answer 5: B. Superheat is suction temperature minus saturation temperature: 52 minus 40 equals 12 degrees F.
  • Question 6 (Ohm's Law): A 24 volt transformer supplies a coil with 12 ohms resistance. Per Ohm's Law (I = E / R), what current flows, and what VA is consumed? A) 0.5 amps, 12 VA. B) 2.0 amps, 48 VA. C) 12 amps, 288 VA. D) 2.0 amps, 24 VA.
  • Answer 6: B. Current I = 24 divided by 12 = 2.0 amps; power = 24 times 2.0 = 48 VA.

Question 7 and How to Score Your HVAC Practice Run

Exhaust duct safety and FBC Mechanical Chapter 5 rules appear on both the Air A and Air B exams.

  • Question 7 (Dryer Exhaust Ducts): Under 2023 FBC Mechanical Sections 504.4 and 504.8.2, clothes dryer exhaust ducts must be constructed of rigid metal with smooth interior surfaces and terminate where? A) Inside an attic space near the soffit. B) Outside the building, with no screws or fasteners protruding more than 1/8 inch into the inside of the duct. C) Into the return air plenum. D) Inside a crawl space.
  • Answer 7: B. Under FBC Mechanical Sections 504.4 and 504.8.2, dryer exhaust must terminate outdoors, and screws or other fasteners that protrude more than 1/8 inch into the inside of the duct are prohibited because they trap lint.
  • Scoring Your Run: Passing either Florida HVAC exam requires 70 percent, so scoring at least 5 out of 7 (71 percent) on this quiz is your target baseline.

Psychrometric chart, calculator, and tabbed 2023 Florida Building Code book on a study desk

Frequently Asked Questions (FAQ)

How many questions are on the Florida Air A vs Air B HVAC exam?

The Class A Air Conditioning Trade Knowledge exam has 130 scored questions with a 7.5 hour time limit, while the Class B exam has 80 scored questions with a 5 hour time limit. Both tests are computer based, open book, and require a minimum score of 70 percent.

What is the tonnage limit for a Class B HVAC license in Florida?

Under Florida Statutes Section 489.105(3)(g), a Certified Class B Air Conditioning Contractor is limited to 25 tons of cooling and 500,000 Btu of heating in any one system, whether residential or commercial. Class A contractors have no tonnage or heating capacity limit.

Can I upgrade from a Class B to a Class A HVAC license later?

Yes. Under Florida Statutes Section 489.111, an active Certified Class B Air Conditioning Contractor with at least one year of proven experience in the Class B classification is eligible to apply for a Class A license after passing the Class A Trade Knowledge exam, without retaking Business and Finance.

How do I access free Florida HVAC practice questions online?

Start with the seven worked questions in this article, then create your free student account on our Free Course page. Registration is 100 percent free with no credit card required and unlocks the License Fix Student Portal and introductory exam prep modules.

Start Your Free Florida HVAC Exam Prep Course Today

Completing a seven question HVAC exam practice test shows you how psychrometrics, code lookups, and statutory rules appear on exam day, but passing a 5 hour or 7.5 hour exam requires timed drilling. Sign up for a free student account right now on our Free Intro to Business and Finance Course page with no credit card required. You will get instant access to the License Fix Student Portal on your phone or computer, Business and Finance video lessons, and extra free contractor practice test questions. When you are ready to prepare for your trade test, explore our Florida Air A Trade Exam Preparation Course, our Florida Air B Trade Exam Preparation Course, and our smarter HVAC study guide.

Pascual, Contractor Licensing Instructor

About Pascual, Contractor Licensing Instructor

Contractor Licensing Instructor

Pascual is a Florida contractor licensing exam prep specialist, with a focus on the Business & Finance and General Contractor exams. He has helped numerous candidates prepare for and pass their state exams, combining technical knowledge of Florida's regulations with practical study strategies. His approach is straightforward and grounded in real experience with the exam format, helping future contractors understand not just the content, but also how to avoid the most common mistakes that trip up candidates.

Contact Us Today